GE Multilin

489 Generator Management Relay

4-35

4 SETPOINTS

4.7 S6 VOLTAGE ELEMENTS

4

4.7.3 VOLTS/HERTZ

PATH: SETPOINTS

ÖØ

S6 VOLTAGE ELEMENTS

ÖØ

VOLTS/HERTZ

The Volts/Hertz elements may be used generator and unit transformer protection. They are active as soon as the magni-
tude and frequency of V

ab

is measurable. The alarm element is definite time; the trip element can be definite time or a

curve. Once the V/Hz measurement V

ab

exceeds the pickup level for the specified time, a trip or alarm will occur. The reset

rate is a linear reset time from the threshold of trip and should be set to match cooling characteristics of the protected
equipment. The measurement of V/Hz will be accurate through a frequency range of 5 to 90 Hz. Settings less than 1.00
only apply for special generators such as short circuit testing machines.

„ VOLTS/HERTZ
„ [ENTER] for more

VOLTS/HERTZ

ALARM: Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5

VOLTS/HERTZ ALARM

PICKUP: 1.00 x Nominal

Range: 0.50 to 1.99

× Nominal in steps of 0.01

VOLTS/HERTZ ALARM

DELAY: 3.0 s

Range: 0.1 to 150.0 s in steps of 0.1

VOLTS/HERTZ ALARM

EVENTS: Off

Range: On, Off

VOLTS/HERTZ

TRIP: Off

Range: Off, Latched, Unlatched

ASSIGN TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

VOLTS/HERTZ TRIP

PICKUP: 1.00 x Nominal

Range: 0.50 to 1.99

× Rated in steps of 0.01

VOLTS/HERTZ TRIP

DELAY: 1.0 s

Range: 0.1 to 150.0 s in steps of 0.1

VOLTS/HERTZ CURVE

RESET RATE: 1.4 s

Range: 0.0 to 999.9 s in steps of 0.1

VOLTS/HERTZ TRIP

ELEMENT: Curve #1

Range: Curve #1, Curve #2, Curve #3, Definite Time

The formula for Volts/Hertz Curve 1 is:

where: T = trip time in seconds

D =

VOLTS/HERTZ TRIP DELAY

setpoint

V = RMS measurement of Vab
F = frequency of Vab
V

NOM

= generator voltage setpoint

F

S

= generator frequency setpoint

Pickup =

VOLTS/HERTZ TRIP PICKUP

setpoint

The V/Hz Curve 1 trip curves are shown on the right
for delay settings of 0.1, 0.3, 1, 3, and 10 seconds.

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

T

D

V F

V

nom

F

s

(

) Pickup

×

-----------------------------------------------------

2

1

----------------------------------------------------------------------

=

, when

V
F

---- Pickup

>

808743A1-X1.CDR

0.01

0.1

1

10

100

1000

1.00

1.20

1.40

1.60

1.80

2.00

Multiples of Volts/Hertz Pickup

10

3

1

0.3

T

IM

E

D

E

LA

Y

S

E

TT

IN

G

T

im

et

oT

ri

p

(s

e

c

ond

s)

0.1