489 Generator Management Relay

GE Multilin

5.6 A5 EVENT RECORDER

5 ACTUAL VALUES

5

The 489 Event Recorder stores generator and system information each time an event occurs. The description of the event
is stored and a time and date stamp is also added to the record. This allows reconstruction of the sequence of events for
troubleshooting. Events include: all trips, any alarm optionally (except Service Alarm, and 489 Not Inserted Alarm, which
always records as events), loss of control power, application of control power, thermal resets, simulation, serial communica-
tion starts/stops and general input control functions optionally.

EVENT01

is the most recent event and

EVENT40

is the oldest event. Each new event bumps the other event records down

until the 40th event is reached. The 40th event record is lost when the next event occurs. This information can be cleared
using

S1 489 SETUP

ÖØ

CLEAR DATA

ÖØ

CLEAR EVENT RECORD

setpoint. The event record will not update if a digital input

programmed as Test Input is shorted.

ANALOG INPUT 2

EVENT01: 0.0 Units

Range: –50000 to 50000

Seen only if the Analog Input is in use.

ANALOG INPUT 3

EVENT01: 0.0 Units

Range: –50000 to 50000

Seen only if the Analog Input is in use.

ANALOG INPUT 4

EVENT01: 0.0 Units

Range: –50000 to 50000

Seen only if the Analog Input is in use.

Table 5–1: CAUSE OF EVENTS

TRIPS

Ambient RTD12 Trip *

Analog I/P 1 to 4 Trip *

Bearing RTD 7 Trip *

Bearing RTD 8 Trip *

Bearing RTD 9 Trip *

Bearing RTD 10 Trip *

Differential Trip

Distance Zone 1 Trip

Distance Zone 2 Trip

Field-Bkr Discr. Trip

Gnd Directional Trip

Ground O/C Trip

Hiset Phase O/C Trip

Input A to G Trip *

Loss of Excitation 1

Loss of Excitation 2

Low Fwd Power Trip

Neg Seq O/C Trip

Neutral O/V Trip

Neut. U/V (3rd) Trip

Offline O/C Trip

Overfrequency Trip

Overvoltage Trip

Phase O/C Trip

Phase Reversal Trip

Reactive Power Trip

Reverse Power Trip

RTD11 Trip *

Sequential Trip

Stator RTD 1 Trip *

Stator RTD 2 Trip *

Stator RTD 3 Trip *

Stator RTD 4 Trip *

Stator RTD 5 Trip *

Stator RTD 6 Trip *

Tachometer Trip

Thermal Model Trip

Underfrequency Trip

Undervoltage Trip

Volts/Hertz Trip

ALARMS (OPTIONAL EVENTS)

Ambient RTD12 Alarm *

Analog I/P 1 to 4 Alarm *

Bearing RTD 7 Alarm *

Bearing RTD 8 Alarm *

Bearing RTD 9 Alarm *

Bearing RTD 10 Alarm *

Breaker Failure

Current Demand Alarm

Gnd Directional Alarm

Ground O/C Alarm

Input A to G Alarm *

Low Fwd Power Alarm

MVA Alarm

Mvar Alarm

MW Alarm

NegSeq Current Alarm

Neut. U/V 3rd Alarm

Neutral O/V Alarm

Open RTD Alarm

Overcurrent Alarm

Overfrequency Alarm

Overvoltage Alarm

Reactive Power Alarm

Reverse Power Alarm

RTD11 Alarm *

Short/Low RTD Alarm

Stator RTD 1 Alarm

Stator RTD 2 Alarm

Stator RTD 3 Alarm

Stator RTD 4 Alarm

Stator RTD 5 Alarm

Stator RTD 6 Alarm

Tachometer Alarm

Thermal Model Alarm

Trip Coil Monitor

Trip Counter Alarm

Underfrequency Alarm

Undervoltage Alarm

VT Fuse Fail Alarm

OTHER

489 Not Inserted

Control Power Applied

Control Power Lost

Dig I/P Waveform Trig

Input A to G Control *

IRIG-B Failure

Serial Comm. Start

Serial Comm. Stop

Serial Waveform Trip

Setpoint 1 Active

Setpoint 2 Active

Simulation Started

Simulation Stopped

Thermal Reset Close

Thermal Reset Open

*

reflects the name that is programmed

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE