4 SETPOINTS

4.11 S10 MONITORING

4

4.11.4 VT FUSE FAILURE

PATH: SETPOINTS

ÖØ

S10 MONITORING

ÖØ

VT FUSE FAILURE

A fuse failure is detected when there are significant levels of negative sequence voltage without corresponding levels of
negative sequence current measured at the output CTs. Also, if the generator is online and there is not significant positive
sequence voltage, it could indicate that all VT fuses have been pulled or the VTs are racked out. If the alarm is enabled and
a VT fuse failure detected, elements that could nuisance operation are blocked and an alarm occurs. These blocked ele-
ments include voltage restraint for the phase overcurrent, undervoltage, phase reversal, and all power elements.

Figure 4–20: VT FUSE FAILURE LOGIC

„ VT FUSE FAILURE
„ [ENTER] for more

VT FUSE FAILURE

ALARM: Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5

VT FUSE FAILURE

ALARM EVENTS: Off

Range: On, Off

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

99ms

99ms

Block
Appropriate
Elements
&
Operate
Alarm
Relay

I / I < 20%

2

1

V / V > 25%

2

1

I > 0.075 x CT

1

V > 0.05 x Full Scale

1

Breaker Status = Online

V < 0.05

Full Scale

1

×

0

0

AND

OR

AND