3 trip coil monitor, 3 trip coil monitor -70 – GE 489 User Manual

Page 120

Advertising
background image

4-70

489 Generator Management Relay

GE Multilin

4.11 S10 MONITORING

4 SETPOINTS

4

4.11.3 TRIP COIL MONITOR

PATH: SETPOINTS

ÖØ

S10 MONITORING

ÖØ

TRIP COIL MONITOR

If the trip coil monitor alarm feature is enabled as latched or unlatched, the trip coil supervision circuitry will monitor the trip
coil circuit for continuity any time that the breaker status input indicates that the breaker is closed. If that continuity is bro-
ken, a trip coil monitor alarm will occur in approximately 300 ms.

If 52 Open/Closed is selected, the trip coil supervision circuitry monitors the trip coil circuit for continuity at all times regard-
less of breaker state. This requires an alternate path around the 52a contacts in series with the trip coil when the breaker is
open. See the figure below for modifications to the wiring and proper resistor selection. If that continuity is broken, a Starter
Failure alarm will indicate Trip Coil Supervision.

Figure 4–19: TRIP COIL SUPERVISION

„ TRIP COIL MONITOR
„ [ENTER] for more

TRIP COIL MONITOR

ALARM: Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5

SUPERVISION OF TRIP

COIL: 52 Closed

Range: 52 Closed, 52 Open/Closed

TRIP COIL MONITOR

ALARM EVENTS: Off

Range: On, Off

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

808727A1.CDR

VALUE OF RESISTOR 'R'

SUPPLY

OHMS

WATTS

48 VDC

125 VDC

250 VDC

10 K

25 K

50 K

2

5

5

TRIP
COIL

TRIP COIL
SUPERVISION

R1 TRIP
CONTACT

F11

E2

F1

E11

52a

TRIP COIL CLOSED SUPERVISION

"52 Closed"

TRIP COIL
SUPERVISION

R1 TRIP
CONTACT

TRIP
COIL

F11

E2

F1

E11

52a

TRIP COIL OPEN/CLOSED SUPERVISION

"52 Open/Closed"

52a

TRIP
COIL

TRIP COIL
SUPERVISION

R1 TRIP
CONTACT

F11

E2

F1

E11

52a

TRIP COIL

OPEN/CLOSED

SUPERVISION

"52 Open/Closed"

WITH MULTIPLE

BREAKER AUX

CONTACTS