489 Generator Management Relay

GE Multilin

A.1 STATOR GROUND FAULT

APPENDIX A

A

Figure A–5: GROUND DIRECTIONAL ELEMENT CONCEPTUAL ARRANGEMENT

The operating principle of this element is quite simple: for internal ground faults the two signals will be 180° out of phase
and for external ground faults, the two signals will be in phase. This simple principle allows the element to be set with a high
sensitivity, not normally possible with an overcurrent element.

The current pickup level of the element can be adjusted down to 0.05

× CT primary, allowing an operate level of 0.25 A pri-

mary if the 50:0.025 ground CT is used for the core balance. The minimum level of V

neutral

at which the element will operate

is determined by hardware limitations and is internally set at 2.0 V.

Because this element is directional, it does not need to be coordinated with downstream protections and a short operating
time can be used. Definite time delays are suitable for this element.

Applications with generators operated in parallel and grounded through a common impedance require special consider-
ations. If only one generator is grounded and the other ones left floating, the directional element for the floating generators
does not receive a correct V

neutral

signal and therefore cannot operate correctly. In those applications, the element makes

use of auxiliary contacts off the grounding switch and the unit breaker to turn the element into a simple overcurrent element,
with the pickup level set for the directional element (note that the ground directional element and the ground overcurrent
elements are totally separate elements). In this mode, the element can retain a high sensitivity and fast operate time since
it will only respond to internal stator ground faults. The table below illustrates the status of different elements under various
operating conditions.

Table A–1: DETECTION ELEMENT STATUS

GENERATOR

CONDITION

UNIT

BREAKER

GROUNDING

SWITCH

ELEMENT

GROUND

DIRECTIONAL

NEUTRAL

OVERVOLTAGE

GROUND

OVERCURRENT

Shutdown

Open

Open

Out-of-service

Out-of-service

In-service

Open Circuit and

grounded

Open

Closed

In-service (but will not

operate due to lack of LO)

In-service

In-service

Loaded and

Grounded

Closed

Closed

In-service

In-service

In-service

Loaded and Not

Grounded

Closed

Open

In service as a simple

overcurrent element

Out-of-service

In-service

808734A1.CDR

GENERATOR

CORE

BALANCE

CT

BREAKER

Aux.

Contact

Grounding
Switch

To Relay

Grounding

Impedance

(Trans. &

Resistor)

Grounding

Switch

Aux. Cont.

G.S.

Status

Breaker

Status

Ground

O/C

Element

Isolating
Transformer

V

Input

neutral

Ground

Directional

Element
(or O/C)

489

Neutral

O/V

Element

Ground
Current
Input

Aux.

Breaker

Advertising