489 Generator Management Relay

GE Multilin

4.9 S8 RTD TEMPERATURE

4 SETPOINTS

4

4.9.4 RTD 11

PATH: SETPOINTS

ÖØ

S8 RTD TEMPERATURE

ÖØ

RTD #11

RTD 11 defaults to Other RTD type. The Other selection allows the RTD to be used to monitor any temperature that might
be required, either for a process or additional bearings or other. There are individual alarm and trip configurations for this
RTD. Trip voting has been added for extra reliability in the event of RTD malfunction. If enabled, a second RTD must also
exceed the trip temperature of the RTD being checked before a trip will be issued. If the RTD is chosen to vote with itself,
the voting feature is disabled. The RTD name may be changed if desired.

„ RTD #11
„ [ENTER] for more

RTD #11 APPLICATION:

Other

Range: Stator, Bearing, Ambient, Other, None

RTD #11 NAME:

Range: 8 alphanumeric characters

RTD #11 ALARM:

Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5.

RTD #11 ALARM

TEMPERATURE: 80°C

Range: 1 to 250°C in steps of 1

RTD #11 ALARM

EVENTS: Off

Range: On, Off

RTD #11 TRIP:

Off

Range: Off, Latched, Unlatched

RTD #11 TRIP VOTING:

RTD #11

Range: RTD #1 to RTD #12

ASSIGN TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

RTD #11 TRIP

TEMPERATURE: 90°C

Range: 1 to 250°C in steps of 1

ENTER

ESCAPE

р

р

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE

MESSAGE

ESCAPE