8 phase differential trip accuracy, A) minimum pickup check, B) single infeed fault – GE 489 User Manual

Page 226: C) slope 1 check, D) slope 2 check, E) directional check, Phase differential trip accuracy -14

Advertising
background image

7-14

489 Generator Management Relay

GE Multilin

7.3 ADDITIONAL FUNCTIONAL TESTS

7 TESTING

7

7.3.8 PHASE DIFFERENTIAL TRIP ACCURACY

These tests will require a dual channel current source. The unit must be capable of injecting prefault cur-
rents and fault currents of a different value. Application of excessive currents (greater than 3

× CT) for

extended periods will cause damage to the relay.

a) MINIMUM PICKUP CHECK

1.

Connect the relay test set to inject Channel X current (I

x

) into the G3 terminal and out of H3 terminal (Phase A).

Increase I

x

until the differential element picks up. Record this value as pickup. Switch off the current. The theoretical

pickup can be computed as follows:

(EQ 7.5)

b) SINGLE INFEED FAULT

2.

Set the I

x

prefault current equal to 0. Set the fault current equal to CT. Apply the fault. Switch off the current. Record the

operating time.

3.

Set the I

x

prefault current equal to 0. Set the fault current equal to 5

× CT. Apply the fault. Switch off the current. Record

the operating time.

c) SLOPE 1 CHECK

4.

Connect the relay test set to inject Channel Y current (I

Y

) into the G6 terminal and out of H6 terminal. The angle

between I

x

and I

Y

will be 180°.

5.

Set pre-fault current, I

x

and I

Y

equal to zero.

6.

Set fault current, I

Y

equal to 1½ CT.

7.

At this value the relay should operate according to the following formula:

(EQ 7.6)

8.

Set fault current, I

x

equal to 0.95

× I

XOP1

. Apply the fault. The relay should operate. Switch off the current.

9.

Set fault current, I

x

equal to 1.05

× I

XOP1

. Apply the fault. The relay should restrain. Switch off the current.

d) SLOPE 2 CHECK

10. Set fault current, I

Y

equal to 2.5

× CT.

11. At this value the relay should operate according to the following formula.

(EQ 7.7)

12. Set fault current, I

x

equal to 0.95

× I

XOP2

. Switch on the test set. The relay should operate. Switch off the current.

13. Set fault current, I

x

equal to 1.05

× I

XOP2

. Switch on the test set. The relay should restrain. Switch off the current.

e) DIRECTIONAL CHECK

14. Set pre-fault current, I

x

and I

Y

equal to 2.5

× CT. At this value the conditions for CT saturation detection are set and the

relay will enable the directional check.

15. Set fault current, I

x

equal to 0.95

× I

XOP2

. Switch on the test set. The relay should restrain. Switch off the current.

16. Repeat Steps 1 through 15 for phases B and C.

NOTE

I

XPU

Pickup setting CT

×

=

I

XOP1

2 Slope 1 setting

2 Slope 1 setting

+

------------------------------------------------- 3 CT

Ч

2

-----------------

Ч

=

I

XOP2

2 Slope 1 setting

2 Slope 1 setting

+

------------------------------------------------- 2.5 CT

Ч

Ч

=