9 ground directional, Ground directional -31 – GE 489 User Manual

Page 81

Advertising
background image

GE Multilin

489 Generator Management Relay

4-31

4 SETPOINTS

4.6 S5 CURRENT ELEMENTS

4

Figure 4–4: DIFFERENTIAL ELEMENTS

4.6.9 GROUND DIRECTIONAL

PATH: SETPOINTS

ÖØ

S5 CURRENT ELEMENTS

ÖØ

GROUND DIRECTIONAL

„ GROUND DIRECTIONAL
„ [ENTER] for more

SUPERVISE WITH

DIGITAL INPUTS: Yes

Range: Yes, No. Seen only if a digital input is assigned to

Ground Switch Status

GROUND DIRECTIONAL

MTA: 0°

Range: 0°, 90°, 180°, 270°

Note: MTA = Maximum Torque Angle

GROUND DIRECTIONAL

ALARM: Off

Range: Off, Latched, Unlatched

ASSIGN ALARM

RELAYS (2-5): ---5

Range: Any combination of Relays 2 to 5

GROUND DIR. ALARM

PICKUP: 0.05 x CT

Range: 0.05 to 20.00

× CT in steps of 0.01

GROUND DIR. ALARM

DELAY: 3.0 sec.

Range: 0.1 to 120.0 sec. in steps of 0.1

GROUND DIR. ALARM

EVENTS: Off

Range: On, Off

GROUND DIRECTIONAL

TRIP: Off

Range: Off, Latched, Unlatched

ASSIGN TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

GROUND DIR. TRIP

PICKUP: 0.05 x CT

Range: 0.05 to 20.00

× CT in steps of 0.01

GROUND DIR. TRIP

DELAY: 3.0 sec.

Range: 0.1 to 120.0 sec. in steps of 0.1

OPERATE

REGION

I

(multiples of CT)

RESTRAINT

I

(m

u

lt

ip

le

s

o

f

CT

)

OP

E

RA

T

E

Slope 2 = 20%

808790A2.CDR

Slope 1 = 10%

Minimum Pickup = 0.10 x CT

1

0.9

0.8

0.7

0.6

0.5

0.4

0.3

0.2

0.1

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

5