GE Multilin

489 Generator Management Relay

4-43

4 SETPOINTS

4.7 S6 VOLTAGE ELEMENTS

4

where: Z

primary

= primary ohms impedance

CT Ratio = programmed CT ratio, if CT ratio is 1200:5 use a value of 1200 / 5 = 240
VT Ratio = programmed VT ratio, if VT ratio is 100:1 use a value of 100

Figure 4–7: LOSS OF EXCITATION R-X DIAGRAM

4.7.10 DISTANCE ELEMENT

PATH: SETPOINTS

ÖØ

S6 VOLTAGE ELEMENTS

ÖØ

DISTANCE ELEMENT

„ DISTANCE ELEMENT
„ [ENTER] for more

STEP UP TRANSFORMER

SETUP: None

Range: None, Delta/Wye

FUSE FAILURE

SUPERVISION: On

Range: On, Off

ZONE #1

TRIP: Off

Range: Off, Latched, Unlatched

ASSIGN ZONE #1 TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

ZONE #1

REACH: 10.0

Ωsec

Range: 0.1 to 500.0

Ωsec in steps of 0.1

ZONE #1

ANGLE: 75°

Range: 50 to 85° in steps of 1

ZONE #1 TRIP

DELAY: 0.4 s

Range: 0.0 to 150.0 s in steps of 0.1

ZONE #2

TRIP: Off

Range: Off, Latched, Unlatched

ASSIGN ZONE #2 TRIP

RELAYS (1-4): 1---

Range: Any combination of Relays 1 to 4

ZONE #2

REACH: 15.0

Ωsec

Range: 0.1 to 500.0

Ωsec in steps of 0.1

ZONE #2

ANGLE: 75°

Range: 50 to 85° in steps of 1

ZONE #2 TRIP

DELAY: 2.0 s

Range: 0.0 to 150.0 s in steps of 0.1