Publication 1757-IN032B-EN-P - April 2001

2-6 Firmware Maintenance Procedures

2. Click Communications

Configure Drivers

3. Click the Virtual Backplane (SoftLogix 58XX) selection in the

Available Drivers list box and click Add New to call up the Add
New RSLinx Driver dialog box.

4. Click OK to accept the default name AB_VBP-1 for the driver.

5. Click Close to close the Configure Drivers dialog box.

6. Click the + (plus) sign next to AB_VBP-1 to expand the Virtual

Backplane tree.

7. Confirm that the 1784-PCIC icon is listed with 3.3 Q28 firmware.

If the revision is at 3.3 Q28, skip to Loading 1757-PLX52 and
TC-MUX021 Boot and Personality Images on page 2-10,
if not go
to the next section Stop All ProcessLogix Applications and
Services on page 2-6.

Stop All ProcessLogix Applications and Services

1. Exit all running ProcessLogix applications, such as Control Builder,

Station, and Network Tools (NTOOLS).

2. Click Start

Settings

Control Panel.

3. Double-click the Services icon.

4. Change ALL the ProcessLogix Services Startup Type to Manual.

To change a Service Startup Type to Manual:

a. Select the Service and click Startup.

b. In the Startup Type field, click the Manual option and click

OK.

The following Services should be changed to Manual Startup:

ProcessLogix ER Replicator (redundant SERVERB node only)

ProcessLogix ER Server

ProcessLogix System Repository

ProcessLogix Control Data Access Server

ProcessLogix Server Daemon

ProcessLogix Server Database

ProcessLogix Server System