Configuring the controlnet supervisory network, Configuring the controlnet supervisory network -31 – Rockwell Automation 1757-SWKIT3200 ProcessLogix R320.0 Installation and Upgrade Guide User Manual

Page 159

Advertising
background image

Publication 1757-IN032B-EN-P - April 2001

Full PC Software Installation Procedures 3-31

7. In the Configure Drivers dialog box, you should see AB_PCIC-1

listed in the Configured Drivers list with the status Running. If the
AB_PCIC-1 driver status is not Running, call Rockwell
Automation Technical Support. Refer to Rockwell Automation
Technical Support in the Preface.

8. Click Close to close the Configure Drivers dialog box.

9. Close RSLinx.

10. Restart the PC.

Configuring the ControlNet Supervisory Network

If this is the first time you have used Network Tools on this PC, refer
to Making First Time Network Tools Settings on page 5-15 a
nd then
continue with this procedure beginning at Step 5.

1. Click Start

Run.

2. Key in this command in the Open entry field:

>ntools -25 -c -nl -pit -pg -u<

and click OK to launch Network Tools.

3. Click OK to acknowledge the warning about monitoring through

Control Builder.

4. Click Resume

to initiate network scan.

5. When network nodes appear under the Desktop tree icon, click the

01 CNB icon.

IMPORTANT

Whenever the 1784-PCIC Network Address is changed,
the 1784-PCIC driver must be stopped and restarted to
complete the change.