5-26 Supplementary Procedures
•
Refer to Control Hardware Installation Guide
⇒
Redundancy Module
Installation and Removal.
•
Refer to Control Hardware Installation Guide
⇒
Communication
Module Installation and Removal.
Checking firmware revision levels
Refer to Upgrading Hardware Component Firmware on page 2-1 to
check/upgrade 1757-PLX52, 1756-CNB, and 1757-SRM firmware.
Creating a Redundant 1757-PLX52
1. Refer to the Control Building Guide
⇒
Hardware Module
Creation
⇒
Creating a Redundant PLX52 controller topic for more
information about configuring a redundant PLX52 in Control
Builder.
2. Once the redundant CPM is created in the Project tab, re-assign the
modules unassigned from the previous non-redundant CPM to the
CEE associated with the new redundant CPM.
3. Load the primary and secondary CPMs and RMs to the
Controllers.
This completes the upgrade to a Redundant Chassis Pair.