Publication 1757-IN032B-EN-P - April 2001

Additional Redundant Server Procedures 4-15

a. With the Full Mode version of the dialog box active, click the

Database Only option.

b. Click Yes to confirm the action and wait for the Server to

change its state.

c. Close the ProcessLogix Server dialog box.

3. Are you using a dual network (LAN) data link with your

redundant Servers?

If the answer is Yes, go to Step 4.

If the answer is No, go to Step 9.

4. Use Windows NT Explorer to locate the redun.hdw file in this

directory path:

C:\Honeywell\server\user

5. Double-click the redun.hdw file to open it in Notepad. Modify the

file to include the following entries for dual data links.

This is only required if you have redundant LANs.

DEL LNK00
ADD LNK00 NETWORK_LINK TYPE=DATA
DEL LNK01
ADD LNK01 NETWORK_LINK TYPE=DATA

The default file definition is for a single network (LAN) data link.

6. Click File

Save to save your changes to the file.

7. Close Notepad.

8. Click File

Close to exit Explorer.

9. Click Start

Run.

IMPORTANT

For information about the required operator actions
for the setup of fast failover, navigate in Knowledge
Builder to Server/Client Configuration
Guide

Configuring and Monitoring Redundant

Server System

Server Redundancy Fast Failover

Configuration topic for HOSTS file and redundant
hardware build details.