Publication 1757-IN032B-EN-P - April 2001

Supplementary Procedures 5-17

5. Do the following in the Options tab.

a. Key in >2< in entry field for Delay between scans (seconds).

b. Select the Periodic (automatic) option.

This means automatic scans are made periodically with the
specified delay between scans.

c. Check Enable Module Version/Revision Checking.

This turns ON the automatic firmware version/revision
detection function. This means Network Tools automatically
detects any incompatible firmware in a given module and
shows the module’s firmware indication in Red instead of
Green on the module’s graphic representation.

d. Check Enable ControlNet Parameter Checking.

This turns on the function for checking ControlNet parameter
settings.

6. Click OK to close the dialog box.

7. Click Resume

to initiate network scan.

8. When network nodes appear under the Desktop tree icon, click the

first CNB or Ethernet driver icon to call up the settings dialog box.

You only have to make these settings on the initial scan of the
system. However, you can access the settings at any time by

clicking the CNB or ENET icon and then clicking Settings

.

9. In the Local Chassis tab, adjust the number in the scroll box to

match the number of slots in your local chassis.