Publication 1757-IN032B-EN-P - April 2001

1-2 System Software Upgrade Procedures

The following table summarizes some upgrade related functions that you
should consider before upgrading the existing system to R320.0.

Consider this:

Because:

New license with
R320.0 ProcessLogix
software

Your existing R300.1 or 310.0 license will not work with
R320.0.

Be certain that you have the R320.0 license numbers on
hand before starting the software installation.

Localization

The localization of an existing system is lost during an
upgrade.

Before starting an upgrade, be certain that you have the
localization toolkit in your language for R320.0.

Remove the current localization update using the Control
Panel Add/Remove Programs function.

Select R200 Language Update to change the language for
the Control Builder application back to the default of US
English.

Save Controller Data

This updates the database with current Controller data.

This is recommended if you plan to make a backup of your
current database.

Refer to Saving Current Controller Data (optional) on
page 1-3.

Back Up R300.0 Server
Data

This provides a path for recovering your current system as a
standard precaution.

Refer to Installing Service Pack 6a for Windows NT 4.0 on
page 1-11.

Have at least 400MB
of Free Disk Space

This allows sufficient disk space to automatically backup
selected system data during the installation process.

Refer to Determining Your Hard Drive Free Space
Requirements on page 1-4.