Publication 1757-IN032B-EN-P - April 2001

5-12 Supplementary Procedures

ODBC data source - Click Start

Settings

Control

Panel

ODBC to verify that your ODBC data source (under

the system DSN tab) is set to “erdb” and the Configure path
points to the ERDB location
(C:\Honeywell\TPS50\System\ER\erdb_a.mdb or
erdb_b.mdb.)

13. Click Start

Settings

Control Panel

Services and verify that all

ProcessLogix services have started correctly (RSLinx, ER Server,
System Repository, Control Data Access). If the Server is
redundant, do not start the ER Replicator service yet.

14. Click Start

Programs

ProcessLogix Server

Start-Stop

ProcessLogix Server and verify that Server is running.

15. Restore the ERDB from the replica ERDB on SERVERA. Do the

following:

If the Server being
restored is:

Then:

a member of a
redundant Server pair

you may need to synchronize the Engineering Repository
database

If changes have been made since the Server was last
backed up, the database should be updated from the copy
on the other Server using the following procedure.

the preferred Primary
Server, SERVERA

A. Restore the replica ERDB from the master ERDB on

SERVERB. At SERVERB, click Start

Programs

ProcessLogix Engineering Tools

DbAdmin.

B. Select Tools

Create New Replica.

C. When prompted, choose to overwrite the existing replica.

the preferred
Secondary Server,
SERVERB

A. Stop ProcessLogix Server (Click Start

Programs

ProcessLogix Server

Start-Stop ProcessLogix Server.)

B. Stop ProcessLogix services. Click Start

Settings

Control Panel

Services and stop ProcessLogix Er Server

(which will also stop System Repository and Control Data
Access.)

C. At SERVERB, delete the recovered ERDB

(C:\Honeywell\TPS50\System\ER\erdb_a.mdb.)

D. At SERVERB, click Start

Programs

ProcessLogix

Engineering Tools

DbAdmin. Click Tools

Recover

Design Master to re-create the ER database from the
replica on SERVERA.

E. Start ProcessLogix services. Click Start

Settings

Control Panel

Services and start ProcessLogix Control

Data Access (which will also start Er Server and System
Repository.)

F. Start ProcessLogix Server (Click Start

Programs

ProcessLogix Server

Start-Stop ProcessLogix Server.)