Installing and connecting redundant chassis – Rockwell Automation 1757-SWKIT3200 ProcessLogix R320.0 Installation and Upgrade Guide User Manual

Page 211

Advertising
background image

Publication 1757-IN032B-EN-P - April 2001

Supplementary Procedures 5-25

15. Click Delete Selected object(s) to delete the selected objects.

16. Click the CPM icon, and click Edit

Delete.

17. Click the Delete Selected object(s) button to delete the

non-redundant CPM.

18. In Project tab, click Tools

Assign to call up the Controller

Assignments dialog box.

Confirm that the check boxes for the selection Show CMs and
Show IOMs are checked.

19. Select the CEE associated with the non-redundant CPM in the

Select a CEE list box.

20. Select all the modules listed in the Assigned Modules list box.

Document the modules you will be unassigning.

21. Click Unassign.

Wait for modules to be unassigned and removed from the
Assigned Modules list box.

22. Click Close and return to the Project tab.

23. Click the CPM icon and click Edit

Delete. Click the Delete

Selected object(s) button to delete the CPM and its associated
CEE.

24. Close Control Builder.

Installing and connecting Redundant Chassis Pair (RCP)
hardware

Refer to the following data in Knowledge Builder for general information
about Controller redundancy and how to install and connect the
1757-PLX52, 1757-SRM Redundancy Module (SRM), and 1756-CNBR
redundant ControlNet Bridge module (CNB).

Refer to Control Builder Components Theory

Controller

Redundancy Functionality before upgrading to a Redundant Chassis
Pair for general information about Controller redundancy and
related terminology.

Refer to Control Hardware Installation Guide

Controller Module

Installation and Removal to install the 1757-PLX52 module.