Upgrading hardware component firmware, Things to check after the upgrade, Things to check after the upgrade -39 – Rockwell Automation 1757-SWKIT3200 ProcessLogix R320.0 Installation and Upgrade Guide User Manual

Page 59

Advertising
background image

Publication 1757-IN032B-EN-P - April 2001

System Software Upgrade Procedures 1-39

Upgrading Hardware
Component Firmware

1. Refer to Loading 1757-PLX52 and TC-MUX021 Boot and

Personality Images on page 2-10 to upgrade the 1757-PLX52 boot
and personality images to the current release level.

2. After upgrading the 1757-PLX52, refer to Upgrading Hardware

Component Firmware on page 2-1 to check if other hardware
components require upgrades.

Making Post ProcessLogix
Software Installation
Checks for a
Non-redundant Server

Things to check after the upgrade

The following table summarizes some items that should be checked
before you begin operating your upgraded ProcessLogix system.

IMPORTANT

Stop! It is mandatory that you check the firmware
revision levels for ALL ProcessLogix hardware
components after a ProcessLogix software installation
and/or a component addition or replacement.

Do not proceed until you have upgraded the firmware.
Then go to the next section, Making Post
ProcessLogix Software Installation Checks for a
Non-redundant Server
.

Check this:

Because:

Station
Configuration File

The original station.ini file is renamed old_station.ini and is
replaced by a new station.ini in the

C:\WINNT directory. Any

changes made to the original file (old_station.ini) need to be made
to the new file (station.ini).

The old default.stn file in the C:\Honeywell\client\station directory
will be overwritten. Any changes made to the original file will need
to be made to the new file.

Station Menu

A new Station menu (menu.txt) is installed. This means any
configurations made to the original Station menu will be lost and
will need to be reconfigured for the new Station menu through
Station.