Re-installing the 1784-pcic driver, Re-installing the 1784-pcic driver -34 – Rockwell Automation 1757-SWKIT3200 ProcessLogix R320.0 Installation and Upgrade Guide User Manual
Page 54

Publication 1757-IN032B-EN-P - April 2001
1-34 System Software Upgrade Procedures
The following Services should be changed to Automatic Startup:
•
ProcessLogix ER Replicator (redundant SERVERB node only)
•
ProcessLogix ER Server
•
ProcessLogix System Repository
•
ProcessLogix Control Data Access Server
•
ProcessLogix Server Daemon
•
ProcessLogix Server Database
•
ProcessLogix Server System
26. Click Start
⇒
Shut Down and select the shutdown the computer
option.
27. Power down the PC.
Re-installing the 1784-PCIC Driver
1. Turn on the PC and logon as plx_user.
2. Click Start
⇒
Programs
⇒
Rockwell Software
⇒
RSLinx
⇒
RSLinx
to call up the Rockwell Software RSLinx window.
3. Click Communications
⇒
Configure Drivers to call up the
Configure Drivers dialog box.
IMPORTANT
If you are configuring a redundant server pair,
configure both SERVERA and SERVERB.
Do not restart the Servers. Return to Re-installing the
1784-PCIC Driver on page 1-55.