Installing the processlogix server, Installing the processlogix server -51 – Rockwell Automation 1757-SWKIT3200 ProcessLogix R320.0 Installation and Upgrade Guide User Manual

Page 71

Advertising
background image

Publication 1757-IN032B-EN-P - April 2001

System Software Upgrade Procedures 1-51

Installing the ProcessLogix Server

1. At the Welcome to ProcessLogix Server Setup window, click Next.

2. Click Yes in the Question box to upgrade the ProcessLogix Server

to R320.0.

3. Click Yes to replace the detected versions of Display Builder,

Quick Builder, and Station.

4. Skip to Step 6 if the Specify Microsoft Excel Directory window

does not appear. Otherwise, click Next to accept the default
directory for Microsoft Excel.

5. Click No in response to the question:

Do you want Microsoft Excel Data Exchange to be allowed to
write to a ProcessLogix Server database?

to disable the Microsoft Excel Data Exchange write option.

6. At the Choose point mode acronyms window, click the Default

acronyms option and click Next.

7. Review the software installation details summarized in the

Confirmation window.

If you need to make changes, click Back to access any previous
entries.

If the details are okay, click Next to begin the Server setup. This
may take 10 to 15 minutes to complete.

ATTENTION

!

We recommend that you answer No to the question:

Do you want Microsoft Excel Data Exchange to be
allowed to write to a ProcessLogix Server database?

If you answer Yes, the write option is enabled and it is
possible for anyone with access to the machine to write
to the Server database.