Publication 1757-IN032B-EN-P - April 2001

2-14 Firmware Maintenance Procedures

6. When the correct file appears in the list box, select it so that it

appears in the File Name entry field.

7. Click Open to start the firmware load and click Yes to confirm

the action.

8. Wait for the load to complete and the 1757-PLX52 or

TC-MUX021 module to reboot to its NODB status as shown in
the module LED display. The Status field in the lower portion of
the Network Tools window tracks the load progress.

9. Click OK to acknowledge the load completion with no errors.

10. Confirm that the LED display on the 1757-PLX52 or TC-MUX021

module shows NODB

11. Repeat the procedures in the Sections entitled Loading boot

image and Loading personality image for other 1757-PLX52 or
TC-MUX021 modules in your network, as required. Be sure to
update the partner 1757-PLX52 module in an RCP system
configuration.

12. Click Network Tools

Exit to close the application. Continue

with other firmware upgrades as applicable in the next Section
or return to upgrade or installation procedures as applicable.