1-18 System Software Upgrade Procedures

Removing the
9904/1784-KTCX15 Card and
Installing the 1784-PCIC
Card

Use the following procedure as a general guide to remove the
9904/1784-KTCX15 drivers for RSLinx from an R300.1 or R310.0
ProcessLogix Server. If you already have a 1784-PCIC card installed, skip
this section.

1. Click Start

Programs

Rockwell Software

RSLinx

RSLinx

to call up the Rockwell Software RSLinx window.

2. Click Communications

Configure Drivers to call up the

Configure Drivers dialog box.

3. Select the AB_KTC-1 in the Configured Drivers list box and click

Configure.

4. Record the AB_KTC-1 Network Address.

5. Click Delete.

6. Close RSLinx and power down the PC.

7. Remove ControlNet cables from the KTCX15 card and remove the

KTCX15 card from the PC.

8. Install the 1784-PCIC card and attach the ControlNet cables.

Refer to the installation instructions, Publication
1784-IN003A-EN-P for details.

ATTENTION

!

Before continuing, you MUST exit all ProcessLogix
applications and stop all ProcessLogix services.

Refer to Stopping ProcessLogix Applications and
Services on page 1-8.

IMPORTANT

If you have redundant servers, you must complete this
procedure on the SERVERB node first. Then complete
the entire procedure again for the SERVERA node.

ATTENTION

!

In order to perform correctly, the 1784-PCIC card
MUST have the PAL part number 99640604. If the
1784-PCIC card does not have this PAL, you must
return your card for the update.

Contact Rockwell Automation Technical Support for
more information. Refer to Rockwell Automation
Technical Support in the Preface.