Step 1 and step 2 – Rockwell Automation 1757-SWKIT3200 ProcessLogix R320.0 Installation and Upgrade Guide User Manual

Page 152

Advertising
background image

Publication 1757-IN032B-EN-P - April 2001

3-24 Full PC Software Installation Procedures

1. Click Start

Programs

Rockwell Software

RSLinx

RSLinx

to open the RSLinx application.

2. Check the application title in the title bar:

If the title is RSLinx Lite, refer to Installing the Activation File
on page 1-27.

If the title is RSLinx OEM you already have the OEM version
installed and you do not have to install the activation file.

For ControlNet Supervisory Networks, skip to Configuring

RSLinx Drivers for ControlNet Supervisory Network on
page 3-24
.

For Ethernet Supervisory Networks, skip to Configuring

RSLinx Drivers for Ethernet Supervisory Network on
page 3-33
.

Configuring RSLinx Drivers
for ControlNet Supervisory
Network

Use the following procedure to configure the ControlNet PCIC drivers
for RSLinx.

ATTENTION

!

If you need to reformat the hard drive, you must first
move the activation file back to the RSLinx Master
Disk using the same general procedure as follows.
Otherwise, the file will be corrupted and you will not
be able to run RSLinx in the OEM mode.

Before you attempt to move the activation file, you
MUST exit all ProcessLogix applications and stop all
ProcessLogix services. Refer to Stop All ProcessLogix
Applications and Services on page 3-27
.

Do not manually copy or move the evrsi.sys file.
Moving/coping the evrsi.sys file will disable the OEM
version of RSLinx.

Always use the EVMOVE.EXE program to move the
evrsi.sys file. If the evrsi.sys file is corrupted or
manually moved, resulting in RSLinx changing to Lite
version, you can visit the Rockwell web site
(http://suppport.automation.rockwell.com/resetcodes
/) to recover the RSLinx activation.

IMPORTANT

If you are using Ethernet for your Supervisory
Network, skip to Configuring RSLinx Drivers for
Ethernet Supervisory Network on page 3-33.