Performance and Capacity Specifications 7-15

Input Module Sample Periods

Output Module Sample Periods

ATTENTION

!

Avoid operator-induced redundant controller
switchovers with I/O that is configured but not
physically present. In a redundant controller, the new
primary 1757-PLX52 infrequently may become mute
or hard fault under stress test conditions involving both
{1} a non-trivial number of repetitive switchovers and
{2} I/O configured in the controller that is not
physically present. The only recovery is to power-cycle
the mute of faulted primary controller.

Table 7.R Input Module Sampling Period Specifications

Module types

Sampling period

Typical Input Module
Includes 1757/1756 input modules 1797-FLEX Ex and 1794-FLEX I/O
input modules, and CN2FFs with exceptions noted below

25 ms

High Density / Non-Isolated Analog Input Module (1756-IF16)

250 ms

RTD Module (1756-IR6I)

50 ms

Thermocouple Module (1756-IT6I)

50 ms

TC-MUX021

250 ms

Digital Input Module used by 5 ms (local only)

1 ms

Note: For CMs which contain associated input channels, it is recommended that the CM execution
period should be set to at least double the input module sampling period.

Table 7.S Output Module Sampling Period Specifications

Output Module Sampling Period Specifications

Module Type

Sampling Period

Typical Output Module
1757/1756 +1797 FLEX EX and 1794-FLEX I/O Output Modules

50 ms