Publication 1757-IN032B-EN-P - April 2001

6-18 New Functions and Features

In the Channel Name field select the channel defined earlier. In the
Definition field type the following:

2 NAME=name ID=id1 STN=id2 MONITOR_ADDR=addr

where:

name

is the name of the controller with a maximum of 10
characters

id1

is the ControlNet MAC address of the first PLC in the
redundant PLC pair

id2

is the ControlNet MAC address of the second PLC in the
redundant PLC pair

addr

is the file and word address in the PLC where backup
status of the PLC is stored, for example: N12:3. Must not
exceed 6 characters.

Using Quick Builder to Configure Points

Quick Builder is used to define and configure points to reference data
in an Allen-Bradley PLC. Points belonging to a redundant
Allen-Bradley controller are defined in the same way as those defined
for other types of connection for Allen-Bradley. For details on defining
and configuring points refer to the Quick Builder online help.

Improved Industrial Shape Files

New versions of some commonly used industrial shapes have been
included in the Pipes area of the Industrial shape gallery in this
release. These new shape files have a reduced memory footprint. The
new shape files are:

Pipebend1.dsp

Pipebend2.dsp

Pipebend3.dsp

Pipebend4.dsp

Pipeflange1.dsp

Pipeflange2.dsp

Pipeflange3.dsp

Pipeflange4.dsp