Publication 1757-IN032B-EN-P - April 2001

System Software Upgrade Procedures 1-57

11. Restart the PC.

Configuring the ControlNet
Supervisory Network

If this is the first time you have used Network Tools on this PC, refer
to Making First Time Network Tools Settings on page 5-15 a
nd then
continue with this procedure beginning at Step 6.

1. Restart SERVERB.

2. On SERVERB, click Start

Run.

3. Key in this command in the Open entry field:

>ntools -25 -c -nl -pit -pg -u<

and click OK to launch Network Tools.

4. Click OK to acknowledge the warning about monitoring through

Control Builder.

5. Click Resume

to initiate network scan.

6. When network nodes appear under the Desktop tree icon, click the

01 CNB icon.

7. In the graphic pane, select the Supervisory Uplink CNB and click

Change ControlNet Parameters

.

8. Change UMax to 24 and click OK.

IMPORTANT

Be certain to update the 1784-PCIC firmware for both
SERVERA and SERVERB.

Once you have completed these procedures for both
SERVERA and SERVERB, you can continue with the
next section, Configuring the ControlNet Supervisory
Network.