Publication 1757-IN032B-EN-P - April 2001

Performance and Capacity Specifications 7-9

User Interface Capacity and
Performance

Table 7.G Operational display update rates

Maximum Continuous Display Update Rate

1 sec

Typical Field Change to Display Update Time with 100 Parameters
Per Display on a Single Station/Server
(Server configured for 1 sec update)

< 2 sec

Typical Display Call Up Time with 100 Parameters on a Single
Station/Server
(Call up time is dependent on display complexity; this excludes
the first initial call up.)

< 2 sec

Maximum Number of Concurrent Users Connected to one Server.
See Table 7.M Server communication NetBIOS session usage on
page 7-12 for i
nformation that may affect the number of Stations
that may be connected simultaneously.

20

Table 7.H Multi-user CB operational limits

Maximum CB Clients connected to single Server

4

Remote Access Service (RAS) support for Multi-User CB

Not Supported

Dial-up Networking support for Multi-User CB

Not Supported

Minimum continuously available Network Bandwidth required for each
multi-user CB Client.

128KB

ATTENTION

!

Viewing the expanded Monitoring Tab Tree View of
the same 1757-PLX52 Controller loaded with more
than 500 total CMs, SCMs and IOMs from more than
one CB client simultaneously, will severely affect the
performance of the 1757-PLX52 Controller’s
communication capability, both to the Server and
Peer-to-Peer.

Using multiple CB clients to load to multiple
controllers simultaneously actually increases the overall
load time. Do not employ this technique as a way to
save time in loading a controller with contents.

Database operations (load, delete, upload, update, etc.)
initiated from a CB client will affect the performance of
applications that run on the backup Server. Remote CB
clients will also be affected by these operations. For
instance, a CB client will experience reduced
performance if another CB client is also connected to
the same Server and has requested a large database
operation.

Advertising