Publication 1757-IN032B-EN-P - April 2001

Firmware Maintenance Procedures 2-7

5. Click Start

Shut Down and select the shutdown the computer

option.

6. Power down the PC.

Continue with the updating of the 1784-PCIC card firmware.

1. Turn on the PC and logon as plx_user.

2. Click Start

Run.

3. Key in this command in the Open entry field:

>C:\Honeywell\TPS50\System\Firmware\1784-PCIC\3_3\Setup.exe.<

4. Click OK.

5. At the Welcome to ControlFLASH Setup window, click Next.

6. Click Next to accept the default location.

7. Uncheck the Yes, I want to view the ControlFLASH readme file.

8. Check Yes, I want to launch ControlFLASH and click Finish.

9. At the Welcome to ControlFLASH window, click Next.

10. Click 1784-PCIC and click Next.

11. Double-click on AB_PCIC1.

12. Confirm that the update revision is 3.3 and click Next.

13. At the Summary window, click Finish.

14. Click Yes to confirm flash.

The card will now execute the 3.3 firmware.

15. Click OK.

When the update is completed, ControlFLASH will report that the
1784-PCIC card failed to report the new revision number. Since the
3.3 firmware requires a different driver than the 1.4 card,
ControlFLASH does not reset the card when the update is
completed. This allows the card to continue functioning as a 1.4
card.