Performance and Capacity Specifications 7-13
Controller Notifications
Controller Redundancy
Table 7.O Controller Notifications Performance
1757-PLX52 Controller Notifications Performance (50 ms and 5 ms CEE)
Maximum number of events (burst condition)
50 events
Maximum number of event/second (sustained)
2/sec
•
Up to a minute between event bursts
ATTENTION
!
The Ethernet Module cannot be used with Controller
Redundancy
Table 7.P Controller Redundancy (50 ms CEE only) Specifications
Controller Redundancy (50 ms CEE only)
Controller models supported
1757-PLX52 only
Control Processing Switchover Interruption Time
500 ms
Redundancy Module Cable Medium
Fiber Optic Cable
Redundancy Module Cable Lengths
1, 3, 10 meters
Redundancy Module Slot Width
2 slots
Initial Synchronization Timer (from Sync Start to Completion)
90 sec
Maximum Elapsed Time Between Commanded Switchover and
Completion of Initial Synchronization
120 sec
Maximum Elapsed Time Between Switchover Due to Power
Cycle of the Primary and Completion of Initial Synchronization
150 sec