Publication 1757-IN032B-EN-P - April 2001

Performance and Capacity Specifications 7-13

Controller Notifications

Controller Redundancy

Table 7.O Controller Notifications Performance

1757-PLX52 Controller Notifications Performance (50 ms and 5 ms CEE)

Maximum number of events (burst condition)

50 events

Maximum number of event/second (sustained)

2/sec

Up to a minute between event bursts

ATTENTION

!

The Ethernet Module cannot be used with Controller
Redundancy

Table 7.P Controller Redundancy (50 ms CEE only) Specifications

Controller Redundancy (50 ms CEE only)

Controller models supported

1757-PLX52 only

Control Processing Switchover Interruption Time

500 ms

Redundancy Module Cable Medium

Fiber Optic Cable

Redundancy Module Cable Lengths

1, 3, 10 meters

Redundancy Module Slot Width

2 slots

Initial Synchronization Timer (from Sync Start to Completion)

90 sec

Maximum Elapsed Time Between Commanded Switchover and
Completion of Initial Synchronization

120 sec

Maximum Elapsed Time Between Switchover Due to Power
Cycle of the Primary and Completion of Initial Synchronization

150 sec