7-18 Performance and Capacity Specifications

Table 7.W 1757-PLX52 Memory Resources and Block Configuration

1757-PLX52 Memory Resources and Block Configuration

Definition: MU = Memory Unit = 1 Kbyte = 1024 bytes

Maximum Available 1757-PLX52 Memory Resources

4000 MU

Maximum Total Number of CMs, SCMs and IOMs Configurable
per 1757-PLX52

1000

Maximum Number of Component Blocks per CM

40

Maximum Total Number of Steps and Transitions
(in all handlers) per SCM

160
(80 Step/Transition pairs)

Table 7.X Typical IOM/CM/SCM Processing and Memory Resource Requirements

Typical IOM/CM/SCM Processing and Memory Resource Requirements

Total Processing Resources (PU/sec) per module are computed as = Processing Resource
Consumption (PU/module execution) / Execution Period (sec/module execution).

Typical Module Types
(FB Content in Parenthesis)

Processing Resource Consumption
(Per Module)

Memory
Resource
Usage
See Notes

50/5 ms CEE
Non-Redundant
(PU/Module
Execution)

50 ms CEE
Redundant
(PU/Module
Execution)

50/5 ms CEE
(MU/Mod)

Typical I/O Module
(Average consumption of available IOMs)

0.3

0.19

0.6

Analog Digital Acquisition Module
(10 AI, 10 DataAcq FBs)

2.9

3.8

7.4

Small Analog Data Acquisition Module
(1 AI, 1 DataAcq FB)

0.47

0.43

1.0

Regulatory Control Module
(1 AI, 1 DataAcq, 1 PID, 1 AO, 6 Logic FBs)

2.8

2.8

3.9

Auxiliary Function Module
(10 Aux. FBs, such as AuxCalc, Totalizer)

4.2

5.1

13.1

Digital Data Acquisition Module
(10 DI, 10 Flag FBs)

1.2

1.2

3.1

Small Digital Data Acquisition Module
(1 DI, 1 Flag FBs)

0.22

0.14

0.6

Device Control Module
(2 DI, 2 DO, 1 DevCtl, 5 Logic FBs)

1.3

1.3

3.1

Logic Control Module
(20 Logic FBs)

1.0

1.0

3.5

Sequence Control Module

(1)

2.0

3.0

55