Publication 1757-IN032B-EN-P - April 2001

1-30 System Software Upgrade Procedures

7. In the Configure Drivers dialog box, you should see AB_PCIC-1

listed in the Configured Drivers list with the status Running. If the
AB_PCIC-1 driver status is not Running, call Rockwell
Automation Technical Support. Refer to Rockwell Automation
Technical Support in the Preface.

8. Click Close to close the Configure Drivers dialog box.

9. Close RSLinx.

10. Restart the PC.

Updating the 1784-PCIC Card Firmware

Determining the 1784-PCIC Firmware Revision

If your 1784-PCIC card is not at 3.3 Q28 firmware revision, you will need
to flash update the card.

If you have ControlNet devices attached to the 1784-PCIC card, do the
following:

1. Click Start

Programs

Rockwell Software

RSLinx

RSLinx

to call up the Rockwell Software RSLinx window.

2. Click Communications

RSWho.

IMPORTANT

Whenever the 1784-PCIC Network Address is changed,
the 1784-PCIC driver must be stopped and restarted to
complete the change.

ATTENTION

!

In order to perform correctly, the 1784-PCIC card
MUST have the PAL part number 99640604. If the
1784-PCIC card does not have this PAL, you must
return your card for the update.

Contact Rockwell Automation Technical Support for
more information. Refer to Rockwell Automation
Technical Support in the Preface.

IMPORTANT

The 1784-PCIC card’s driver must be listed as available
in RSLinx before running the ControlFLASH update.

If you have not installed the 1784-PCIC driver, refer
to Installing the 1784-PCIC Driver on page 1-29.