1-40 System Software Upgrade Procedures

Reconfiguring Other RSLinx Clients

Other applications which utilized the deleted 9904-KTCX15 driver must
be reconfigured for the 1784-PCIC driver.

Reloading the 1757-PLX52 Database

Use the following procedure to log on and check Control Builder
operation after the R320.0 software is installed.

1. Click Start

Programs

ProcessLogix Engineering

Tools

Control Builder.

2. In the Login dialog box, make these entries:

a. Key in >mngr< as the default User Name.

b. Key in >mngr1< as the default Password.

c. Key in >localhost< in the Server Name field.

3. Click OK.

4. In the Project tab, confirm that the components of your configured

control strategy are listed in the Root directory.

If using:

You must:

NI-FBUS

reconfigure the NI-FBUS communications software to use
the new 1784-PCIC card

navigate in Knowledge Builder to Linking
Device Implementation Guide

Installation

Configure the NI-FBUS Interface for more

information

use AB_PCIC-1 for the Driver name

SCADA points

reconfigure the Channel for the 1784-PCIC

navigate in Knowledge Builder to

Controller References

Allen-Bradley Controller Reference

Defining a

Allen-Bradley Channel for more information.

use AB_PCIC-1 for the Driver name

ATTENTION

!

If you also upgraded from a non-redundant
1757-PLX52 to a redundant 1757-PLX52, you must
delete the existing CPM and its associated CEE from
the Project tab, reconfigure a new 1757-PLX52 and its
associated CEE, and reassign the components before
you download the CPM to the Controller.