At step 6, Step 10 o – Rockwell Automation 1757-SWKIT3200 ProcessLogix R320.0 Installation and Upgrade Guide User Manual

Page 127

Advertising
background image

Publication 1757-IN032B-EN-P - April 2001

Firmware Maintenance Procedures 2-17

4. Click OK to launch the Network Tools application.

5. Click OK to acknowledge the warning about monitoring through

Control Builder.

6. Click Resume

to initiate network scan.

7. Click any CNB icon under the Desktop tree and wait for the

graphic of the chassis to appear in the Detail pane.

8. In the graphic of your chassis, click the CNB module with the

Network Address selected above.

9. Click Change ControlNet

to call up the Keeper Values dialog

box.

10. Confirm that the values listed for the parameters under the

Changes Tab on the dialog box match the following settings and
key in new values, as required.

TIP

This may be the only module that appears in
the chassis graphic at this time.

Advertising