Publication 1757-IN032B-EN-P - April 2001

2-12 Firmware Maintenance Procedures

Loading Boot Image

1. Click the 1757-PLX52 or TC-MUX021 module in the graphic of

the chassis configuration in the Detail pane. If required, select
another CNB icon to find the chassis that contains a 1757-PLX52 or
TC-MUX021 module.

2. Click Firmware

to initiate the firmware update.

3. Click Yes to acknowledge the Warning prompt.

4. If the LED on the 1757-PLX52 or TC-MUX021 module is not in its

Ready (RDY) state, click Yes to issue a Stop (Shutdown)
command to the 1757-PLX52 or TC-MUX021 module. Otherwise,
go to Step 5. Wait for the 1757-PLX52 or TC-MUX021 module to
reboot to its RDY state as shown in the module LED display.

5. To load the boot image to a 1757-PLX52, locate the cpmboot2.pcm

boot file. See Table 2.A on page 2-2.

6. To load the boot image to a TC-MUX021, locate the simboot.pcm

boot file. See Table 2.A on page 2-2.

This example illustrates loading boot image to a 1757-PLX52.

7. When the correct file appears in the list box, select it so that it

appears in the File Name entry field.

8. Click Open to start the firmware load and click Yes to confirm

the action.

9. Wait for the load to complete and the 1757-PLX52 or

TC-MUX021 module to reboot to its ALIVE status as shown in