Restarting redundant servers, Setting up secondary server (serverb) node – Rockwell Automation 1757-SWKIT3200 ProcessLogix R320.0 Installation and Upgrade Guide User Manual

Page 177

Advertising
background image

Publication 1757-IN032B-EN-P - April 2001

Additional Redundant Server Procedures 4-13

Restarting Redundant
Servers

Use the following procedure to restart SERVERA and then SERVERB.

1. Restart the SERVERA node.

2. On the SERVERA node, right-click in the taskbar to open the

popup menu and click Task Manager to call up the Windows NT
Task Manager dialog box.

3. Click the Performance tab in the dialog box.

4. Monitor the CPU Usage until the value displayed goes below the

90 to 100% threshold.

This assures proper startup time of ProcessLogix services on the
SERVERA node before restarting the SERVERB node.

5. Click File

Exit Task Manager.

6. Restart the SERVERB node.

Setting up Secondary
Server (SERVERB) node

Use the following procedures to set up the Secondary SERVERB node.

Setting up the Redundant ERDB

After updating the 1784-PCIC or Ethernet card (on SERVERA and
SERVERB), complete the following procedure on SERVERB only:

1. Click Start

Programs

ProcessLogix Engineering Tools

DBADMIN.

2. Click Tools

Create a New Replica.

a. Click OK to Make Replica of ERDB at the Primary Server.

b. If prompted to stop the ER Replicator service, click Yes.

c. If prompted to overwrite any existing files, click Yes.

4. Click OK at Stopping ER Replication Service.

ATTENTION

!

The following procedure assumes that you have
completed the previous procedures in this section for
both the SERVERA (Primary) and SERVERB
(Secondary) nodes.

Advertising