Rockwell Automation 1757-SWKIT3200 ProcessLogix R320.0 Installation and Upgrade Guide User Manual
Page 180

Publication 1757-IN032B-EN-P - April 2001
4-16 Additional Redundant Server Procedures
10. Key in this command in the Open entry field:
>cmd<
and click OK to open the DOS window.
11. At DOS prompt, key in:
>cd \Honeywell\server\user<
and press <Enter>.
12. Key in this command:
>hdwbld redun.hdw<
and press <Enter>.
The hdwbld utility reads the text file [redun.hdw] and adds the
hardware definitions to the Server database.
If you are using a dual LAN, be certain that you change the default
redun.hdw file as noted in Step 5 to Step 8.
13. Check that no hardware build errors are listed. If errors are listed,
be sure the Server state is Database Only and retry.
14. Key in this command:
>exit<
and press <Enter> to exit DOS.
Configuring the Time Service
1. On the SERVERB node, click Start
⇒
Run.
TIP
Configure the time service only on SERVERB. If you
are configuring SERVERA, skip to Setting Up
Primary Server (SERVERA) Node on page 4-19.