Publication 1757-IN032B-EN-P - April 2001

Full PC Software Installation Procedures 3-27

If the revision is at 3.3 Q28, skip to Configuring the ControlNet
Supervisory Network on page 3-31, if
not go to Stop All
ProcessLogix Applications and Services on page 3-27.

If you do not have ControlNet devices connected to the 1784-PCIC, you
can verify the firmware revision using the virtual backplane. Do the
following:

1. Click Start

Programs

Rockwell Software

RSLinx

RSLinx

to call up the Rockwell Software RSLinx window.

2. Click Communications

Configure Drivers

3. Click the Virtual Backplane (SoftLogix 58XX) selection in the

Available Drivers list box and click Add New to call up the Add
New RSLinx Driver dialog box.

4. Click OK to accept the default name AB_VBP-1 for the driver.

5. Click Close to close the Configure Drivers dialog box.

6. Click the + (plus) sign next to AB_VBP-1 to expand the Virtual

Backplane tree.

7. Confirm that the 1784-PCIC icon is listed with 3.3 Q28 firmware.

If the revision is at 3.3 Q28, skip to Configuring the ControlNet
Supervisory Network on page 3-31
, if not continue with the next
section Stop All ProcessLogix Applications and Services on page
3-27.

Stop All ProcessLogix Applications and Services

1. Exit all running ProcessLogix applications, such as Control Builder,

Station, and Network Tools (NTOOLS).

2. Click Start

Settings

Control Panel.

3. Double-click the Services icon.

4. Change ALL the ProcessLogix Services Startup Type to Manual.

To change a Service Startup Type to Manual:

a. Select the Service and click Startup.

b. In the Startup Type field, click the Manual option and click OK.

The following Services should be changed to Manual Startup:

ProcessLogix ER Replicator (redundant SERVERB node only)