Publication 1757-IN032B-EN-P - April 2001

System Software Upgrade Procedures 1-19

Upgrading
ProcessLogix Software on
a Non-redundant Server
Only

About Upgrading Software on the Server

ProcessLogix now automates most of the migration tasks from a previous
version of the system to the current version. The migration
enhancements support error handling and recovery from migration
problems.

While the ProcessLogix R320.0 software CD supports several platforms,
this procedure covers upgrading the ProcessLogix Software from R300.1
or R310.0 to R320.0 on the Server. In this case, the following components
are installed in succession once you start the installation setup.

RSLinx OEM 2.2

Engineering Tools

Server/Client (Display Builder, Station, and Server)

ProcessLogix Server Upgrade

All files included with the migration wizard will be included as part of the
installation package for the Engineering Tools media included in the
Engineering Tools directory of the ProcessLogix CD. The files that
comprise this utility will be installed into the default location
C:\Honeywell\TPS50\System\ER\Migrate.

IMPORTANT

If you are upgrading a redundant Server pair, refer
to Upgrading ProcessLogix Software on a Redundant
Server Pair on page 1-45
.

ATTENTION

!

Be certain that your process is off control before you
begin any upgrade procedure. This means the
1757-PLX52 should be in the Idle state.