Re-installing the 1784-pcic driver, Re-installing the 1784-pcic driver -30 – Rockwell Automation 1757-SWKIT3200 ProcessLogix R320.0 Installation and Upgrade Guide User Manual
Page 158

Publication 1757-IN032B-EN-P - April 2001
3-30 Full PC Software Installation Procedures
26. Click Start
⇒
Shut Down and select the shutdown the computer
option.
27. Power down the PC.
Re-installing the 1784-PCIC Driver
1. Turn on the PC and logon as plx_user.
2. Click Start
⇒
Programs
⇒
Rockwell Software
⇒
RSLinx
⇒
RSLinx
to call up the Rockwell Software RSLinx window.
3. Click Communications
⇒
Configure Drivers to call up the
Configure Drivers dialog box.
4. Click the 1784-PCIC(S) for ControlNet devices selection in the
Available Drivers list box and click Add New to call up the Add
New RSLinx Driver dialog box.
5. Click OK to accept the default name AB_PCIC-1 for the driver.
6. In the Configure 1784-PCIC window, enter 20 for the Network
Address and click OK.
IMPORTANT
If you are configuring a redundant Server pair,
configure both SERVERA and SERVERB. DO NOT
RESTART the Servers. Return to Configuring the
ControlNet Supervisory Network on page 4-10.