Publication 1757-IN032B-EN-P - April 2001

Additional Redundant Server Procedures 4-11

6. When network nodes appear under the Desktop tree icon, click the

01 CNB icon.

7. In the graphic pane, select the Supervisory Uplink CNB and

click Change ControlNet Parameters

.

8. Change UMax to 24 and click OK.

9. Click Yes to confirm the action.

10. Click OK.

11. Close NTOOLS.

Updating the 1784-PCIC Network Address

1. On SERVERB, click Start

Programs

Rockwell

Software

RSLinx

RSLinx to call up the Rockwell Software

RSLinx window.

2. Click Communications

Configure Drivers to call up the

Configure Drivers dialog box.

3. Select AB_PCIC-1 in the Configured Drivers list box and click

Configure.

4. In the Configure 1784-PCIC window, enter 23 for the new

Network Address for the PCIC and click OK.

5. Restart SERVERB.

ATTENTION

!

Before continuing, you MUST exit all ProcessLogix
applications and stop all ProcessLogix services on
the SERVERB node.

Refer to Stopping ProcessLogix Applications and
Services on page 1-8.

ATTENTION

!

Before continuing, you MUST exit all ProcessLogix
applications and stop all ProcessLogix services on
the SERVERA node.

Refer to Stopping ProcessLogix Applications and
Services on page 1-8.