Page 114

4 Start-Up Programming & Operation
114
YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide
Refer to the following table to install the inrush current suppression circuit for battery.
Table 34 Installation of the Inrush Current Suppression Circuit for Battery
Voltage
<1> Select the appropriate relay referring to the following calculation even if the battery voltage or main power current is applied.
Drive Model
CIMR-LU
Resistor
Relay
200 V
2A0215
1.0
Ω, 80 W
2A0283
1.0
Ω, 80 W
2A0346
1.0
Ω, 80 W
2A0415
1.0
Ω, 80 W
400 V
4A0150
1.0
Ω, 120 W
4A0180
1.0
Ω, 220 W
4A0216
1.0
Ω, 220 W
4A0260
1.0
Ω, 220 W
4A0304
1.0
Ω, 220 W
4A0370
1.0
Ω, 500 W
4A0450
2.0
Ω, 1000 W
4A0605
2.0
Ω, 1000 W
575V
5A0099
2.0
Ω, 220 W
5A0130
2.0
Ω, 220 W
5A0172
2.0
Ω, 440 W
5A0200
2.0
Ω, 440 W
Load current of battery (A) =
Motor rated power (kW)
× Operation frequency when running battery (Hz) × 2 × 1000
Battery voltage (Vdc)
× 0.6 (Motor efficiency) × Motor rated frequency (Hz)
YEA_common