Refer to the following table to install the inrush current suppression circuit for battery.

Table 34 Installation of the Inrush Current Suppression Circuit for Battery

Voltage

<1> Select the appropriate relay referring to the following calculation even if the battery voltage or main power current is applied.

Drive Model

CIMR-LU

Resistor

Relay

200 V

2A0215

1.0

Ω, 80 W

<1>

2A0283

1.0

Ω, 80 W

2A0346

1.0

Ω, 80 W

2A0415

1.0

Ω, 80 W

400 V

4A0150

1.0

Ω, 120 W

4A0180

1.0

Ω, 220 W

4A0216

1.0

Ω, 220 W

4A0260

1.0

Ω, 220 W

4A0304

1.0

Ω, 220 W

4A0370

1.0

Ω, 500 W

4A0450

2.0

Ω, 1000 W

4A0605

2.0

Ω, 1000 W

575V

5A0099

2.0

Ω, 220 W

5A0130

2.0

Ω, 220 W

5A0172

2.0

Ω, 440 W

5A0200

2.0

Ω, 440 W

Load current of battery (A) =

Motor rated power (kW)

× Operation frequency when running battery (Hz) × 2 × 1000

Battery voltage (Vdc)

× 0.6 (Motor efficiency) × Motor rated frequency (Hz)