◆ L: Protection Functions

L parameters provide protection to the drive and motor, including control during momentary power loss, Stall Prevention,
frequency detection, fault reset, overtorque detection, torque limits, and other types of hardware protection.

■

L1: Motor Protection

■

L2: Undervoltage Detection

No.

Name

Description

Setting

L1-01

<5> Default setting is determined by the control mode (A1-02).

<44> Available in drive software versions PRG: 7017 or later.

Motor Overload Protection
Selection

0: Disabled
1: General purpose motor (standard fan cooled)
2: Drive dedicated motor with a speed range of 1:10
3: Vector motor with a speed range of 1:100
5: PM motor with constant torque characteristics

Default:

<5>

Min: 0
Max: 5

L1-02

Motor Overload Protection
Time

Sets the motor thermal overload protection (oL1) time.

Default: 1.0 min
Min: 0.1 min
Max: 5.0 min

L1-03

<44>

Motor Overheat Alarm
Operation Selection (PTC
thermistor input)

Sets operation when the motor temperature analog input (H3-02 or H3-10 = E)
exceeds the oH3 alarm level.
0: Ramp to stop
1: Coast to stop
2: Emergency Stop (Fast Stop) (decelerate to stop using the deceleration time in C1-
09)
3: Alarm only (“oH3” will flash)

Default: 3
Min: 0
Max: 3

L1-04

<44>

Motor Overheat Fault
Operation Selection (PTC
thermistor input)

Sets stopping method when the motor temperature analog input (H3-02 or H3-10 = E)
exceeds the oH4 fault level.
0: Ramp to stop
1: Coast to stop
2: Emergency Stop (Fast Stop) (decelerate to stop using the deceleration time in C1-
09)

Default: 1
Min: 0
Max: 2

L1-05

<44>

Motor Temperature Input
Filter Time (PTC
thermistor input)

Adjusts the filter for the motor temperature analog input (H3-02 or H3-10 = E).

Default: 0.20 s
Min: 0.00 s
Max: 10.00 s

L1-13

Continuous Electrothermal
Operation Selection

0: Disabled
1: Enabled

Default: 1
Min: 0
Max: 1

No.

Name

Description

Setting

L2-05

<9> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. Multiply value by 2.875 for 600 V class drives.

<15> Default setting value is dependent on the setting for the input voltage (E1-01).

Undervoltage Detection
Level (Uv)

Sets the DC bus undervoltage trip level.

Default:

<9> <15>

Min: 150 Vdc
Max: 210 Vdc

<9>