L: Protection Functions

L parameters provide protection to the drive and motor, including control during momentary power loss, Stall Prevention,
frequency detection, fault reset, overtorque detection, torque limits, and other types of hardware protection.

L1: Motor Protection

L2: Undervoltage Detection

No.

Name

Description

Setting

L1-01

<5> Default setting is determined by the control mode (A1-02).

<44> Available in drive software versions PRG: 7017 or later.

Motor Overload Protection
Selection

0: Disabled
1: General purpose motor (standard fan cooled)
2: Drive dedicated motor with a speed range of 1:10
3: Vector motor with a speed range of 1:100
5: PM motor with constant torque characteristics

Default:

<5>

Min: 0
Max: 5

L1-02

Motor Overload Protection
Time

Sets the motor thermal overload protection (oL1) time.

Default: 1.0 min
Min: 0.1 min
Max: 5.0 min

L1-03

<44>

Motor Overheat Alarm
Operation Selection (PTC
thermistor input)

Sets operation when the motor temperature analog input (H3-02 or H3-10 = E)
exceeds the oH3 alarm level.
0: Ramp to stop
1: Coast to stop
2: Emergency Stop (Fast Stop) (decelerate to stop using the deceleration time in C1-
09)
3: Alarm only (“oH3” will flash)

Default: 3
Min: 0
Max: 3

L1-04

<44>

Motor Overheat Fault
Operation Selection (PTC
thermistor input)

Sets stopping method when the motor temperature analog input (H3-02 or H3-10 = E)
exceeds the oH4 fault level.
0: Ramp to stop
1: Coast to stop
2: Emergency Stop (Fast Stop) (decelerate to stop using the deceleration time in C1-
09)

Default: 1
Min: 0
Max: 2

L1-05

<44>

Motor Temperature Input
Filter Time (PTC
thermistor input)

Adjusts the filter for the motor temperature analog input (H3-02 or H3-10 = E).

Default: 0.20 s
Min: 0.00 s
Max: 10.00 s

L1-13

Continuous Electrothermal
Operation Selection

0: Disabled
1: Enabled

Default: 1
Min: 0
Max: 1

No.

Name

Description

Setting

L2-05

<9> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. Multiply value by 2.875 for 600 V class drives.

<15> Default setting value is dependent on the setting for the input voltage (E1-01).

Undervoltage Detection
Level (Uv)

Sets the DC bus undervoltage trip level.

Default:

<9> <15>

Min: 150 Vdc
Max: 210 Vdc

<9>