H4-01

Terminal FM Monitor
Selection

Selects the data to be output through multi-function analog output terminal FM.
Set the desired monitor parameter to the digits available in U -

. For example,

enter “103” for U1-03.

Default: 102
Min: 000
Max: 999

H4-02

Terminal FM Gain

Sets the signal level at terminal FM that is equal to 100% of the selected monitor
value.

Default: 100.0%
Min: -999.9%
Max: 999.9%

H4-03

Terminal FM Bias

Sets the bias value added to the terminal FM output signal.

Default: 0.0%
Min: -999.9%
Max: 999.9%

H4-04

Terminal AM Monitor
Selection

Selects the data to be output through multi-function analog output terminal AM.
Set the desired monitor parameter to the digits available in U -

. For example,

enter “103” for U1-03.

Default: 103
Min: 000
Max: 999

H4-05

Terminal AM Gain

Sets the signal level at terminal AM that is equal to 100% of the selected monitor
value.

Default: 50.0%
Min: -999.9%
Max: 999.9%

H4-06

Terminal AM Bias

Sets the bias value added to the terminal AM output signal.

Default: 0.0%
Min: -999.9%
Max: 999.9%

H4-07

Terminal FM Signal Level
Selection

0: 0 to 10 V
1: –10 to 10 V

Default: 0
Min: 0
Max: 1

H4-08

Terminal AM Signal Level
Selection

0: 0 to 10 V
1: –10 to 10 V

Default: 0
Min: 0
Max: 1