4 start-up programming & operation, Table 28 expla ins the sequence in each time zone – Yaskawa CIMR-LU Drives User Manual

Page 87

Advertising
background image

4 Start-Up Programming & Operation

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

87

S

tart-U

p

Prog

rammin

g

&

Op

er

at

io

n

4

Table 28

explains the sequence in each time zone.

Table 28 Time Zones for Brake Sequence without Torque Compensation at Start

Brake Sequence Using Torque Compensation

If a load measuring device is installed in the elevator, an analog input can be used to input a torque compensation value to
the drive. This function requires one of the closed loop control modes (CLV or CLV/PM). To use torque compensation,
one of the analog input terminals must be configured to provide the torque compensation signal (H3-

= 14).

Figure 46

is a timing chart for a brake sequence using torque compensation.

Figure 41

Figure 46 Brake Sequence Using Torque Compensation at Start

Time Zone

Description

t1

Up or Down command is issued.
Safe Disable terminals H1-HC and H2-HC must be set and Baseblock must be disabled (digital inputs set to H1-

= 8/9).

Speed reference must be selected by multi-function input terminals.
Output contactor control signal is set (H2-

= 51) by the drive.

Drive waits for the “Motor Contactor Feedback” signal (H1-

= 56) to be issued. If the motor contactor feedback is not

received within t1, or if the feedback signal is on before the contactor control command has been issued, an SE1 fault is triggered.

If the motor contactor feedback signal is not used, then the drive waits for the operation start delay time set in S1-10 to pass, then

proceeds to the next step.

t2

After the delay time set in S1-10 has passed, the drive outputs current to the motor.

DC Injection Braking or Position Lock begins.
After the brake release delay time set in S1-06 has passed, the drive sets the “Brake Control” output (H2-

= 50) in order to

release the brake.

t3

DC Injection Braking or Position Lock will continue until:

the time S1-04 has elapsed, or

the time S1-06 has elapsed if S1-06 > S1-04 (this setting should be avoided since the motor could be driven against the applied

brake).

t4

The drive accelerates up to the selected speed. The speed is kept constant until the leveling speed is selected.

t5

Leveling speed is selected. The drive decelerates to the leveling speed and maintains that speed until the Up or Down command is

removed.

t6

The Up or Down signal is cleared. The drive decelerates to zero speed.

t7

The motor speed reaches the zero speed level (S1-01).

DC Injection Braking or Position Lock is then executed for the time set in S1-05.
After the delay time to close the brake set in S1-07 has passed, the drive clears the “Brake Control” output (H2-

= 50). The

brake applies.

t8

The drive continues DC Injection or Position Lock until the time S1-05 has passed. When S1-05 has passed the drive output is

shut off.

t9

After the delay for the magnetic contactor set in S1-11 has passed, the drive resets the output terminal set for “Output Contactor

Control” (H2-

= 51).

The Safe Disable Inputs can be cleared and Baseblock can be enabled.

S3-14 (Torque
Compensation
Diminish Speed)

Speed

t1

t2

t3

t4

t5

t6

t7

t8

t9

Selected Speed

d1-26
(Leveling Speed)

S1-10

(Up/Down Command

Delay Time)

Torque Compensation at Start

S1-04

(DC Injection/

Position Lock

Time at Start)

300%Torque

S3-10 (Starting

Torque Compensation

Increase Time)

S1-07

(Brake

Close
Delay

Time)

S1-05

(DC Injection

Braking/

Position Lock at stop)

S1-11
(Output Contactor
Open Delay Time)

Torque Compensation
Fades Out with S3-15
at S3-14.

Position Lock

Position Lock

Enabled

Up/Down Command

Output Contactor Control

(H2-

= 51)

Motor Contactor Response

(H1-

= 56)

Brake Control (H2-

= 50)

Safe disable (terminals H1/H2 on)

and Baseblock off (H1-

= 8/9)

Latch value from analog input

TOEP_C710616_38F_5_0.book 87 ページ 2013年12月4日 水曜日 午前9時56分

Advertising