Yaskawa CIMR-LU Drives User Manual

Page 227

Advertising
background image

C Standards Compliance

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

227

St

an

dar

d

s

Co

mplia

nce

C

4A0060

<1>

R/L1, S/L2, T/L3

3

4 to 3

M8

9 to 11

(79.7 to 97.4)

U/T1, V/T2, W/T3

3

4 to 3

–, +1

4 to 1

B1, B2

6 to 3

6

6

4A0075

<1>

R/L1, S/L2, T/L3

2

3 to 1/0

M8

9 to 11

(79.7 to 97.4)

U/T1, V/T2, W/T3

2

3 to 1/0

–, +1

3 to 1/0

+3

6 to 1/0

4

6 to 4

4A0091

<1>

R/L1, S/L2, T/L3

1/0

2 to 1/0

M8

9 to 11

(79.7 to 97.4)

U/T1, V/T2, W/T3

1

2 to 1/0

–, +1

3 to 1/0

+3

4 to 1/0

4

6 to 4

4A0112

<1>

R/L1, S/L2, T/L3

3/0

1/0 to 4/0

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

2/0

1/0 to 4/0

–, +1

1/0 to 4/0

+3

3 to 4/0

4

4

4A0150

<1>

R/L1, S/L2, T/L3

4/0

3/0 to 4/0

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

4/0

3/0 to 4/0

–, +1

1 to 4/0

+3

1/0 to 4/0

4

4 to 2

4A0180

<1>

R/L1, S/L2, T/L3

300

2 to 300

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

300

2 to 300

–, +1

1 to 250

+3

3 to 3/0

4

4 to 300

4A0216

<1>

R/L1, S/L2, T/L3

400

1 to 600

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

400

1/0 to 600

–, +1

3/0 to 600

+3

1 to 325

2

2 to 350

4A0260

<1>

R/L1, S/L2, T/L3

500

2/0 to 600

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

500

2/0 to 600

–, +1

3/0 to 600

+3

1 to 325

M10

18 to 23

(159 to 204)

2

2 to 350

M12

32 to 40

(283 to 354)

4A0304

<1>

R/L1, S/L2, T/L3

4/0

× 2P

3/0 to 600

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

4/0

× 2P

3/0 to 600

–, +1

4/0 to 600

+3

3/0 to 600

M10

18 to 23

(159 to 204)

1

1 to 350

M12

32 to 40

(283 to 354)

Model

CIMR-LU

Terminal

Recommended

Gauge

AWG, kcmil

Applicable Gauge

AWG, kcmil

Screw

Size

Tightening Torque

N m (lb.in.)

TOEP_C710616_38F_5_0.book 227 ページ 2013年12月4日 水曜日 午前9時56分