4 start-up programming & operation – Yaskawa CIMR-LU Drives User Manual

Page 90

Advertising
background image

4 Start-Up Programming & Operation

90

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

After setting load conditions 1 and 2, perform a trial run. If required, parameter S3-12 can be set up to add a bias to the
load sensor input when riding in a Down direction (default: 0.0%, same torque compensation characteristics in up and
down direction).

Figure 48

illustrates the effect of torque compensation on the settings of S3-12 and S3-27 through S3-

30.

Figure 43

Figure 48 Torque Compensation at start for the Elevator in Up and Down Direction

S3-30

S3-27

S3-28

(Torque Compensation
Value with Load Condition 2)

Torque Compensation
at Start for the Elevator
in the Down Direction

S3-29

(Analog Input
from Load Sensor
with Load
Condition 1)

(Torque Compensation Value
with Load Condition 1)

During Load Condition 2

Torque Compensation
at Start for the Elevator
in the Up Direction

S3-12 (Starting Torque
Compensation Bias during Lowering)

(Analog input
from Load Sensor
with Load Condition 2)

Analog Input Voltage (V)

During Load Condition 1

0

TOEP_C710616_38F_5_0.book 90 ページ 2013年12月4日 水曜日 午前9時56分