Multi-Function Analog Outputs

The H4 parameters assign functions to analog output terminals FM and AM. Select the function for these terminals by
entering the last three digits of the desired U monitor. For a list of analog output functions, refer to

U: Monitors on

page 206

.

Accel/Decel Ramp and Jerk Settings

Acceleration and deceleration ramps are set using the C1-

parameters. Use the C2-

parameters to adjust the jerk

at the start of acceleration or deceleration.

Figure 41

explains how accel/decel ride and jerk settings can be used to adjust the ride profile.

Figure 37

Figure 41 Accel/Decel Ramp and the Jerk Function

Units used to set the acceleration and deceleration ramp as well as the Jerk function change with the setting of parameter
o1-03.

Elevator Emergency Stop

Start condition for Elevator Emergency Coast to Stop

An emergency coast to stop is performed when the Up or Down command is cleared and all of the following conditions
are met.

• Parameter b1-03 (Stopping Method Selection) is set to 4.
• Parameter d1-18 (Speed Reference Selection Mode) is set to 0 or 3.
• Parameter b1-01 (Speed Reference Selection) is set to 1.
• The Up/Down command is cleared and U1-05 (Speed Feedback) is equal to or greater than S1-26 (Emergency Stop

Start Level).

Elevator Emergency Stop Timing Chart

A timing chart for Elevator Emergency Coast to Stop and normal Ramp to Stop appears in

Figure 42

and

Figure 43

.

Figure 38

Figure 42 With Up/Down command cleared and U1-05

S1-26

C1-02

C2-01

C2-03

C2-04

C2-05 (Jerk Below Leveling Speed)

d1-26 (Leveling Speed)

C2-02

(Jerk at

Accel End)

(Jerk at

Accel Start)

C1-01

(Accel Ramp 1)

(Decel Ramp 1)

(Jerk at

Decel Start)

(Jerk at

Decel End)

Speed

Selected Speed

S1-11
(Output Contactor Open
Delay Time)

S1-26

Emergency Stop

Start Level

DC Injection Braking/
Position Lock at Start

Coast to Stop

Up/Down Command

Safe disable (terminals H1/H2 on)

or Baseblock off (H1-

= 8/9)

H2-

= 51 (Output Cont. Contr.)

H2-

= 50 (Brake Control)

Enabled