L5: Automatic Fault Reset

L6: Torque Detection

No.

Name

Description

Setting

L5-01

Number of Auto Reset
Attempts

Sets the number of times the drive may attempt to reset after the following faults
occur: GF, LF, oC, ov, rr, oH1, oL1, oL2, oL3, oL4, UL3, UL4.

Default: 0
Min: 0
Max: 10

L5-02

Fault Output Operation
during Auto Reset

0: Fault output not active.
1: Fault output active during reset attempt.

Default: 0
Min: 0
Max: 1

L5-06

Undervoltage Fault Reset
Selection

0: Same as L5-01 condition
1: Always automatically reset UV1

Default: 0
Min: 0
Max: 1

No.

Name

Description

Setting

L6-01

Torque Detection Selection
1

0: Disabled
1: oL3 detection only active during speed agree, operation continues after detection
2: oL3 detection always active during run, operation continues after detection
3: oL3 detection only active during speed agree, output shuts down on an oL3 fault
4: oL3 detection always active during run, output shuts down on an oL3 fault
5: UL3 detection only active during speed agree, operation continues after detection
6: UL3 detection always active during run, operation continues after detection
7: UL3 detection only active during speed agree, output shuts down on an oL3 fault
8: UL3 detection always active during run, output shuts down on an oL3 fault

Default: 0
Min: 0
Max: 8

L6-02

Torque Detection Level 1

Sets the overtorque and undertorque detection level.

Default: 150%
Min: 0%
Max: 300%

L6-03

Torque Detection Time 1

Sets the time an overtorque or undertorque condition must exist to trigger torque
detection 1.

Default: 0.1 s
Min: 0.0 s
Max: 10.0 s

L6-04

Torque Detection Selection
2

0: Disabled
1: oL4 detection only active during speed agree, operation continues after detection
2: oL4 detection always active during run, operation continues after detection
3: oL4 detection only active during speed agree, output shuts down on an oL4 fault
4: oL4 detection always active during run, output shuts down on an oL4 fault
5: UL4 detection only active during speed agree, operation continues after detection
6: UL4 detection always active during run, operation continues after detection
7: UL4 detection only active during speed agree, output shuts down on an oL4 fault
8: UL4 detection always active during run, output shuts down on an oL4 fault

Default: 0
Min: 0
Max: 8

L6-05

Torque Detection Level 2

Sets the overtorque and undertorque detection level.

Default: 150%
Min: 0%
Max: 300%

L6-06

Torque Detection Time 2

Sets the time an overtorque or undertorque condition must exist to trigger torque
detection 2.

Default: 0.1 s
Min: 0.0 s
Max: 10.0 s