6 Periodic Inspection & Maintenance

YASKAWA ELECTRIC TOEP C710616 38F YASKAWA AC Drive L1000A Quick Start Guide

143

Pe

ri

odic

Inspe

c

ti

on &

Maint

ena

nc

e

6

Periodic Maintenance

The drive has Maintenance Monitors that keep track of component wear. This feature provides advance maintenance
warning and eliminates the need to shut down the entire system for unexpected problems. The drive allows the user to
check predicted maintenance periods for the components listed below.

• Cooling Fan, Circulation Fan, Control Board Cooling Fan
• Electrolytic Capacitors
• Inrush Prevention Circuit
• IGBTs

For replacement parts, contact the distributor where the drive was purchased or contact Yaskawa directly.

Replacement Parts

Table 42

contains the estimated performance life of components that require replacement during the life of the drive. Only

use Yaskawa replacement parts for the appropriate drive model and revision.

Table 42 Estimated Performance Life

NOTICE: Estimated performance life based on specific usage conditions. These conditions are provided for the purpose of replacing

parts to maintain performance. Some parts may require more frequent replacement due to poor environments or rigorous use. Usage

conditions for estimated performance life:

Ambient temperature: Yearly average of 40

°C (104°F) (IP00 enclosure)

Load factor: 80% maximum

Operation time: 24 hours a day

Circuit Boards

Check for any odor, discoloration, and rust. Make
sure connections are properly fastened and that no
dust or oil mist has accumulated on the surface of the
board.

• Fix any loose connections.
• If an antistatic cloth or vacuum plunger cannot

be used, replace the board.

• Do not use any solvents to clean the board.
• Remove foreign particles and dust by sucking

them out with a vacuum cleaner to avoid
touching parts.

• The drive has few serviceable parts and may

require complete drive replacement.

Cooling System Periodic Inspection

Cooling Fan,
Circulation Fan,
Control Board
Cooling Fan

• Check for abnormal oscillation or unusual noise.
• Check for damaged or missing fan blades.

• Clean or replace the fan.

Heatsink

Inspect for dust or other foreign material collected on
the surface.

Remove foreign particles and dust by sucking
them out with a vacuum cleaner to avoid touching
parts.

Air Duct

Inspect air intake and exhaust openings. They must
be free from obstruction and properly installed.

• Visually inspect the area.
• Clear obstructions and clean air duct as

required.

Display Periodic Inspection

Digital Operator

• Make sure data appears on the operator properly.
• Inspect for dust or other foreign material that may

have collected on surrounding components.

• Contact a Yaskawa representative if there is any

trouble with the display or keypad.

• Clean the digital operator.

Component

Estimated Performance Life

Cooling Fan, Circulation Fan

<1> The drive has few serviceable parts and may require complete drive replacement.

10 years

Electrolytic Capacitors

10 years

<1>

Inspection Area

Inspection Points

Corrective Action