S6: Error Detection

S5-13

Direct Landing Minimum
Speed Level

Sets the speed level for the start of Direct Landing.
Direct Landing is essentially disabled if the starting speed for Direct Landing is less
than the maximum output speed multiplied by this parameter (E1-04

× S5-13).

Default: 20%
Min: 0%
Max: 100%

<36> When the length units are set for inches (o1-12 = 1), the setting range becomes 0.00 to 650.00 inches.

<37> When the length units are set for inches (o1-12 = 1), the setting range becomes 0.00 to 393.00 inches.

No.

Name

Description

Setting

S6-01

<7> Default setting value is determined by the digital operator display unit selection (o1-03). The default is normally 1.5 m/s2, but when o1-03 = 6,

the default becomes 5.0 ft/s

2

(Setting Range: 0.0 to 50.0 ft/s

2

).

<44> Available in drive software versions PRG: 7017 or later.

Motor Contactor Response
Error (SE1) Detection/
Reset Selection

0: Detect during stop, SE1 must be manually reset
1: Detect during stop, SE1 can be automatically reset
2: No SE1 detection

Default: 0
Min: 0
Max: 2

S6-02

Starting Current Error
(SE2) Detection Delay
Time

Sets a delay time for detecting SE2.

Default: 200 ms
Min: 0.00 ms
Max:
[S1-04]-[S1-06]

S6-03

<44>

SE2 Detect Current Level

Sets the level of current applied to the motor when the Brake Control command is
activated, as a percentage of the Motor No-load Current (E2-03).

Default: 25%
Min: 0%
Max: 100%

S6-04

Output Current Error (SE3)
Detection Delay Time

Sets a delay time for detecting SE3.

Default: 200 ms
Min: 0 ms
Max: 5000 ms

S6-05

Brake Response Error
(SE4) Detection Time

Sets a delay time for detecting SE4.

Default: 500 ms
Min: 0 ms
Max: 10000 ms

S6-10

Overacceleration Detection
Level

If the elevator car accelerates at an abnormal rate, the drive triggers an overspeed fault
(dv6) and has the motor coast to stop. Parameter S6-10 determines the acceleration
rate that triggers a fault.

Default:

<7>

Min: 0.0 m/s

2

Max: 20.0 m/s

2

<7>

S6-11

Overacceleration Detection
Time

Sets a primary delay for detecting overacceleration.

Default: 50 ms
Min: 0 ms
Max: 5000 ms

S6-12

Overacceleration Detection
Selection

0: Always enabled
1: During run only

Default: 0
Min: 0
Max: 1

S6-15

Speed Reference Loss
Detection

Enabled or disables detection for speed reference missing (FrL).
0: Disabled
1: Enabled

Default: 1
Min: 0
Max: 1

S6-16

Restart after Baseblock
Selection

0: No restart after Baseblock/Safe Torque-Off
1: Restart after Baseblock/Safe Torque-Off

Default: 0
Min: 0
Max: 1

No.

Name

Description

Setting